Edge Reactive Calculator

AC Power Factor Correction & Capacitor Bank Sizer

Calculate required kVAR correction, three-phase delta capacitor bank capacitance (microfarads), and line current reduction to eliminate utility power factor penalty charges.

Input Parameters

Auto-calculates on change
Quick Scenario Presets:

Live Edge Calculation

< 5ms latency
Required Reactive Compensation (kVAR)
55.32 kVAR
Capacitance Per Phase (Delta uF)
212.30 uF
Line Current Reduction
33.76 Amps
Correction Posture
Capacitor Bank Compensated from 0.75 to 0.95 PF
Capacitor Bank Compensated from 0.75 to 0.95 PF

Underlying Computational Formula

Q_c (kVAR) = P (kW) * [tan(acos(PF_1)) - tan(acos(PF_2))]; C (uF/phase) = Q_c / (3 * 2 * pi * f * V^2) * 10^6; Delta_I = P / (sqrt(3) * V) * (1/PF_1 - 1/PF_2)

Frequently Asked Questions

How does the AC Power Factor Correction & Capacitor Bank Sizer calculate outputs?

This engine executes deterministic calculations on the Cloudflare edge runtime using the standard formula: Q_c (kVAR) = P (kW) * [tan(acos(PF_1)) - tan(acos(PF_2))]; C (uF/phase) = Q_c / (3 * 2 * pi * f * V^2) * 10^6; Delta_I = P / (sqrt(3) * V) * (1/PF_1 - 1/PF_2). Calculations execute in under 10ms with zero client-side JavaScript hydration lag.